6 specifications of pulse input module, Specifications of pulse input module -20 – Yokogawa DA100 User Manual

Page 89

Advertising
background image

IM DA100-01E

4-20

4.6

Specifications of Pulse Input Module

Style Number: S5
Model Code, Number of Input Channels, Terminal Configuration and Shortest
Measurement Interval

Model Code

Number of Channels

Terminal Configuration

Shortest Measurement
Interval

DU600-11

10

Screw

0.5 s*

*: The interval between data updates is fixed to one second.

Method of Input

Potential with reference to the shared voltage of the COMMON line within the same module

Types of Input

Voltage-free contact or open collector (TTL or transistor)

Measurement Modes

RATE (instantaneous count mode): Outputs the prescaled value of the count of pulses imposed
over the last one-second interval of measurement.
GATE (instantaneous turn-on time mode): Outputs the prescaled values of the contact's turn-on
(make) and turn-off (break) times (on = 1; off = 0) over the last one-second interval of
measurement.

Note

The computing function (computational expression: TLOG.PSUM (XXX)) should be used when
integrating an every-second count or turn-on time (maximum count/turn-on time: 99999999).

Input Range

0 to 6,000 pulses, or 0 to 10 pulses (if the filter is on) for voltage-free input.
Ratio of make at input: 35 to 65% at the maximum frequency (ratio of make = closed-contact
time/(closed-contact time + open-contact time)

× 100)

Minimum input pulse width: 60

µs (whether the contact is closed or open)

Measuring Accuracies
Reference operation conditions

temperature: 23

±2°C; humidity: 55 ±10% RH; supply voltage 90 to 250 VAC (AC power supply)

/10 to 32 VDC (DC power supply); supply frequency: 50/60

±1% (AC power supply); warm-up

time: at least 30 minutes; when operating, the system must not adversely affect the operation of
other equipment.
Count:

±1 pulse (for integration, ±(1 scan + 1 second) at the start of measurement and

±(1 scan +

1.5 seconds) at the end of measurement)
Turn-on time:

±100-ppm accuracy for judgment of one-second-interval sampling; for integration,

±(1 second + 1 scan) at the start of measurement and

±(100 ppm of rdg. + 1.5 seconds + 1 scan) at

the end of measurement
Module-to-module error:

±(3 seconds + 1 pulse) for count and

±(200 ppm + 3 seconds) for turn-

on time

Note

It takes a maximum of 2 seconds for normal measured values to be output when the power is turned on,

when the measurement mode is changed or when the setting for turning on/off the filter is changed. The

DR recorder indicates a value representative of “no data” (

on the display, or 8005H for the

binary format or a faulty data value for the ASCII format in the case of output to the communication line)

until the normal measured values are output.

Filter

Removes chatter of up to 5 ms (can be turned on or off on a channel basis).

Input Signal Levels

Open contact: 200

Ω maximum

Closed contact: 100 k

Ω minimum

Normal Operating Temperature/Humidity Range

0˚ to 50˚C
20 to 80% RH for an ambient temperature range of 0˚ to 40˚C or 10 to 50% RH for 40˚ to 50˚C
(non-condensing)

Normal Operating Magnetic-field Strength

400 A/m maximum