11 retransmission module, Retransmission module -29 – Yokogawa DA100 User Manual

Page 98

Advertising
background image

IM DA100-01E

4-29

4

Specifications

4.11 Retransmission Module

Style number: S10
Model code, number of output points, output signal, output range, terminal type

Model Number of Output Points Output Signal

Output Range

Terminal Type

DT500-11 10ch 1 to 5 VDC

0.8 to 5.4 VDC

screw

DT500-21 2ch 4 to 20 mADC

3.2 to 21.6 mADC

screw

Load resistance

DT500-11: 10 k

Ω or more

DT500-21: 600

Ω or less

Load capacitance

0.22 mF or less

Load Inductance

100 mH or less

Output accuracy (under reference operation conditions)* * *

±0.2% of Span

Calibration period

One year

Temperature coefficient

0.01% of Span/

°C

Highest resolution

DT500-11: 12 bit (approx. 1.43 mV)

DT500-21: 12 bit (approx. 5.86 mA)

Normal operating temperature/humidity

0 to 50

°C

20 to 80%RH for 0 to 40

°C and 10 to 50%RH for 40 to 50 °C (no condensation)

Update interval of output values

Same as the measurement interval
However, depending on the number of modules that are connected, the specified computational
expression, and the condition of the external storage medium, the output value may not be
updated at the measurement interval.

Output during SKIP

DT500-11; 0.05 V or less
DT500-21; 0.15 mA or less

Output filter

First order low pass filter in 10 levels (time constant in the range 4 ms to 3 s) can be applied to the
output value with respect to the changes in the measured data, computed data, and the
communication input value.

Insulation resistance

Across output terminals and ground: 20 M

Ω or more (500 VDC)

Withstand voltage

Across output terminals and ground: 500 VDC for 1 minute

Across channels

DT500-11: No insulation across channels (COM shared)
DT500-21: Insulation across channels (500 VDC, 1 minute)

Power consumption

Included in the value of the main unit or sub-unit.

Dimensions

Approximately 57(W)

×137(H) ×68(D) mm

Weight

DT500-11: Approximately 0.35 kg
DT500-21: Approximately 0.3 kg

Installation category (overvoltage category)

CAT II (IEC1010)