Installation and Wiring

Step 2 : Change the position of the noise source.

A) Leakage magnetic flux of transformer:

Φ

= strong

Φ

= weak

Move the instrument to a location
where the influence from magnetic
flux is weak.

B) Sparks

strong electromagnetic
radiation

weak electrogmagnetic
radiation

Move the instrument to a location
where the influence from electro-
magnetic radiation is weak.

spark

• Grounding: a decrease of impedance

The grounding method is the point of common mode noise suppression.

Equipment

under

measurement

(EUM)

DA100

ec

ec'

EUM

DA100

EUM

DA100

(if grounding is difficult)

or

The difference in the potential to the ground between EUM

and the DA100 may cause a ground current, resulting in noise.

Equalize the potentials to the ground so

that the common mode noise becomes zero.

One-point grounding

Potential equalization

The basic means to obtain stable measurement is to set the circuit potential with proper
grounding. Thus, potential equalization is the means to be adopted only when grounding is
impossible.

2.9 Countering Noise