Yokogawa DA100 User Manual

Page 59

Advertising
background image

IM DA100-01E

2-38

· Relay noise suppression

R

Dc external
power supply

Contact

Diode

connect to the relay
coil terminal (socket)
directly.

(

)

(

)

Relay

the relay coil rating must
be as low as possible.

<DC relay>
• To prevent noise and protect the contact,
connect the diode to the relay coil terminal
directly.
• In addition to the above measure, reduce
the rated voltage of the relay circuit as
much as possible for higher reliability.
• It is necessary to choose a diode that
matches the relay. Generally, a diode
whose rated rectifying current is at least
three times the current flowing through
the relay coil must be used.
And the rated reverse voltage must be at
least three time the operating voltage.

(Note) Across the relay or solenoid coil, a counter-electromotive force is produced by an

inductive load. This phenomenon may damage the contact or, as the noise source,
cause a malfunctioning of the equipment, and have an unfavorable effect on the
entire system.

Surge suppresser circuit

connect to the
relay socket
terminal directly.

(

)

C

R

C=0.01 to 1

µ

F

Must withstand a voltage
of at least three times
the operating voltage.
R=0.3Re to 1Re

Re=Relay coil's DC resistance

<AC relay>
• If a relay contact is connectd to the input
of the system components, apply the
measure shown in the figure at the right
to the relay coil. Otherwise, a counter-
electromotive force produced across the
coil may be induced on the contact side
through the relay's internal coupling or
coupling between the lines, and may
cause a malfunctioning of the equipment.

· Others (isolation from noise source: for hot line measurement)

(Hot line)

Power transistor

(Vcc)

Wrap

At high temperatures

At low temperatures

Mylar isolation film

Adhesive copper
foil tape

Adhesion

Anti-Noise Measures for PC Connection

When connecting the DA100 to a PC, it is recommended to apply ferrite cores (e.g. ZCAT3035-
1303 from TDK) to the interface cable as a noise countering measure. Apply a ferrite core on
both sides of the cable as shown below, when the noise persists, apply more ferrite cores.

Personal
computer

DA100

Ferrite core

Function grounding
terminal

2.9 Countering Noise