Wiring Input Signal Lines (to Universal and DCV/TC/DI input modules)
Terminals
Screw type terminal
Clamp type terminal*
2
+
-
A
B
b
DC voltage • TC •
contact
RTD*
1
A
B
b
Channel1
Channel2
Channel10
Channel2
Channel4
Channel1
Channel3
Channel9
Channel10
+
-
*1 There are no RTD
input terminals on
the DCV/TC/DI input
module and digital
input module.
*2 There is no clamp
type terminal for
digital input module.
Wiring Diagram
DC voltage input
Compensation lead
DC current input
Shunt resistor
Note:For 4 to 20mA input, shunt
resistance value should
be 250
Ω
±
0.1%
10
Ω
* max./leadwire
Three wire resistances
should be approx. equal.
*10
Ω
max. for Pt100
Ω
and
Pt50
Ω
, 1
Ω
max. for Cu10
Ω
.
DC input
RTD input
TC input
DC voltage input/DI input (contact)
b
A
B
A
b
B
+
-
+
-
+
-
+
-
+
-
2.6 Connecting the Signal Lines