Connecting the Retransmission Signal Lines (Retransmission Module)

Processing of Faulty Data

You cam set the output value that corresponds to abnormal measured balues, computed values,
and communication input value using the dip switch of the retransmission module.

Output Type

Output Value

Switch1

Switch2

Switch3

Approx. 0 V (0.05 V or less)

ZERO

OFF

OFF

or approx. 0 mV (0.15 mA or less)

-5%

-OVER

ON

OFF

(0.8 V or 3.2 mA)

+110%

+OVER

OFF

ON

(5.4 V or 21.6 mA)

Value immediately before

Previous value

ON

ON

the faulty data occurence

Data are processed as faulty data in the following cases:
• When the power of the expanded model main unit switches OFF.
• When the measurement channel that is retransmitting experiences the following:

The module of the corresponding measurement channel is removed from the unit.
The power of the unit to which the corresponding channel is connected is removed.

Terminals

Channel 1

- +

Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Channel 9
Channel 10

- +

Channel 1

SW1

SW3

ON

OFF

SW2

Channel 2

DT500-11

DT500-21

2.6 Connecting the Signal Lines