Connection example: sk tu4-pbr to sk 205e, 24v dc – NORD Drivesystems BU0220 User Manual

Page 23

Advertising
background image

2 Assembly and installation

BU 0220 GB-0912

Subject to technical amendments

23

2.2.2.2 Control connections of the SK TU4-PBR(-...)

The double spring-loaded terminal bar of the bus connection unit is colour coded, and therefore indicates the
three different potential levels.

Terminals 1 and 2 have the same potential as the 24V terminals of the system bus level (e.g. Terminal 11).
However, electrical connection between these terminals is only implemented by mounting the bus module onto
the bus connection unit. Terminals 1 and 2 must only be used to supply sensors. Looping of a 24V supply must
not be performed via these terminals (1 and 2).

A separate power source can be used for the supply of the DOs. However, it is possible to implement the
supply of the DOs by bridging 24V 2 and 0V 2 to one of the terminals of the system bus level (24V and 0V).
However, in this case it should be noted that there is an increased risk of introducing interference into the bus
cables.

Connection of the sensors and actuators is made via the terminal bar. Alternatively, the SK TU4-PBR-M12
enables the connection of the digital I/Os via the M12 round plug connector (5 pin socket, A-coded) mounted
on the front.

Double use of the inputs via the terminal bar and the M12 round plug connector must be avoided.

Field bus level
PROFIBUS DP

System bus level and digital inputs

Digital outputs

24V

PB B

IN

PB A

IN

0V-B

RTS

24V

(as 1)

24V

(as 1)

0V

GND

0V

GND

DIN 1

0V

GND

24V

(as 1)

DIN 2

0V

GND

24V

(as 1)

24V 2

DO 1

0V 2

1

3

5

7

9

11

13

15

17

19

21

23

25

27

29

31

33

35

2

4

6

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

24V

(as 1)

PB B

OUT

PB A

OUT

0V-B

(as 8)

+5V B

24V

(as 1)

Sys +

Sys -

0V

GND

DIN 3

0V

GND

24V

(as 1)

DIN 4

0V

GND

24V

(as 1)

0V 2

DO 2

0V 2

Connection example: SK TU4-PBR to SK 205E

SK 205E…-Connection unit (SK TI4…)

SK TU4-

PBR…-Connection unit (SK TI4-TU-BUS)

Voltage

Source

24V DC

PROFIBUS
Subscriber

X-1

PROFIBUS
Subscriber

X+1

Terminal block of the bus Adapter Unit
SK TI4-TU-BUS and assignment of functions

Potential level: Field bus

Potential level: System bus

Potential level: DOs

Advertising