PROFIBUS DP

– Supplementary manualfor NORD Frequency Inverter SK 2xxE

32

Subject to technical amendments

BU 0220 GB-0912

3.1.2.2 PROFIBUS DP displays

The status of the PROFIBUS DP module is indicated by the BR and BE LEDs.

LED
(dual colour)

BR

Bus Ready

LED
(dual colour)

BE

Bus Error

Meaning

... Slow flashing = 2Hz (0.5s cycle)

OFF

OFF

Technology unit not ready, no control voltage or
 system error is indicated
Details: LED flashing code: DS and DE

(Section 3.1.2.1 "Module-specific displays").

ON (green)

OFF

Normal operation, cyclic data exchange via PROFIBUS DP

Flashing 0.5s
(green)

OFF

Technology unit not yet configured from DP master, no cyclic data
exchange

 PROFIBUS DP cable not connected

 Address error

 DP master in STOP

 Hardware configuration fault
(e.g. more than 4 frequency inverters are to be accessed)

ON (red):

ON (red):

Communication timeout

 "Address monitoring time" in DP master expired

ON (red):

Flashing 0.5s
(red)

Communication timeout

 Timeout in process data reception
the time set in parameter (P151) has expired, without new process

data being received

Flashing 0.5s
(red)

Flashing 0.5s
(red)

No communication between technology unit and DP master

Incorrect address range

(Address can be set with DIP switch,

Permissible range: 3 .. 125)

 Module faulty