7 PROFIBUS DP data transfer

BU 0220 GB-0912

Subject to technical amendments

59

7.2 PROFIBUS DP PPO types

For cyclic data traffic, the Parameter- Process data Object (PPO) with which the process data (PZD) and
parameters (PKW) are transferred from the DP master to the frequency inverter is defined. The frequency inverter
can process PPO types 1, 2, 3 or 4.

Type

Task

PPO1

extended parameter data telegram with 32 bit parameter values and process data

PPO2

Telegram with extended process data (main and two auxiliary setpoint values) and 32 bit parameter
value

PPO3

Process data telegram with main setpoint value without parameter data

PPO4

extended process data telegram with main and auxiliary setpoint values without parameter data

PPO3 and PPO4 are purely process data objects for applications which do not require parameter processing.

Note:

A PLC can normally only consistently transfer double words by means of I/O memory access. For
longer data formats (PKW channel always / PZD data with PPO2 or PPO4) system functions (e.g.
SFC 14, consistent data reading / SFC15, consistent data writing) must be used.

Structure of PPO types

PKW

PZD

PKE

IND

PWE

PWE

PZD1

PZD2

PZD3

PZD4

STW

SW1

SW2

SW3

ZSW

IW1

IW2

IW3

1. word

2. word

3. word

4. word

5. word

6. word

7. word

8. word

PPO 1

PPO 2

1. word

2. word

3. word

4. word

PPO3

PPO4