7.3 Example telegrams

7.3.1

Switch-

on disabled → Standby

A frequency inverter is to be switched from the "Switch-on disabled" status (STW Bit 0

– 0), which is active

when the device is switched on, to the "Standby" status (STW Bit 0 = 1). The PPO type 1 (Section 7.2) is used,
however only the PZD channel is considered.

Procedure:

1) Check last status word (e.g. ZSW 0B 70)

2) Generate control word (STW 04 7E)

3) Check response telegram (ZSW 0B 31)

Procedure - Details

1) Check last status word (ZSW 0B 70)

word

5

6

Byte

8

9

10

11

Designation

ZSW

IW1

Value

0B

70

00

00

Bit

Value

Value

HEX

Meaning

15

0

0

Parameter set Bit 1 off

14

0

Parameter set Bit 0 off

13

0

Reserved

12

0

Rotation left is off

11

1

W

Rotation right is on

10

0

Reference value undershot

9

1

Bus controller

8

1

Setpoint = actual value

7

0

7

No warning

6

1

Starting disabled

5

1

No emergency stop

4

1

Voltage not disabled

3

0

0

No fault

2

0

Operation disabled

1

0

Not ready for operation

0

0

Not on standby

2) Generate control word (STW 04 7E)

The frequency inverter is set to Standby status with the following telegram.

word

5

6

Byte

8

9

10

11

Designation

STW

SW1

Value

04

7E

00

00