PROFIBUS DP

– Supplementary manualfor NORD Frequency Inverter SK 2xxE

42

Subject to technical amendments

BU 0220 GB-0912

5.1.2

Control clamp parameter (P400)

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P420

… [-01]

...

… [-04]

Digital inputs 1 to 4

0 ... 77

{ [-01] = 01 }

{ [-02] = 02 }

{ [-03] = 04 }

{ [-04] = 05 }

In the SK 200E, up to 4 freely programmable digital inputs are available. The only restriction is
with the versions SK 215E and SK 235E. Here, the fourth digital input is always the input for the
function "Safe Stop".

… [-01] = Digital input 1 (DIN1), Enable right as factory setting, control terminal 21

… [-02] = Digital input 2 (DIN2), Enable left as factory setting, control terminal 22

… [-03] = Digital input 3 (DIN3), fixed frequency 1 (P465 [-01]) as factory setting,

control terminal 23

… [-04] = Digital input 4 (DIN4), fixed frequency 2 (P465 [-02]) as factory setting,

(not with SK 215/235E  "Safe Stop"), control terminal 24

Various functions can be programmed. For the complete list, please refer to the SK 200E
frequency inverter manual (BU0200).

NOTE:

The additional digital inputs of the field bus group are managed via parameter (P480).

Excerpt...

Value

Function

Description

Signal

00

No function

Input switched off.

---

14

1

Remote control

With bus system control, Low level switches the control to control
via control terminals.

High

1

Also effective for bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS-Interface)