3 supplementary parameters (p500) – NORD Drivesystems BU0220 User Manual

Page 44

Advertising
background image

PROFIBUS DP

– Supplementary manualfor NORD Frequency Inverter SK 2xxE

44

Subject to technical amendments

BU 0220 GB-0912

5.1.3

Supplementary parameters (P500)

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P509

Source Control Word

S

0 ... 4

{ 0 }

Selection of the interface via which the FI is controlled.

0 = Control terminals or keyboard control** with the SimpleBox (if (P510)=0), the

ParameterBox or via BUS I/O Bits.

1 = Only control terminals *, the FI can only be controlled via the digital and analog input

signals or via the Bus I/O Bits.

2 = USS control word *, the control signals (enable, rotation direction, etc.) are transferred

via the RS485 interface, the setpoint via the analog input or the fixed frequencies.

3 = System bus *, the control signals (enable, direction of rotation, ...) are transferred via the

system bus (the field bus module and the frequency inverter communicate via the
system bus). I.e. the setting "3" - "System bus" must be selected in parameter (P509)
for control of the frequency inverter via the field bus.

4 = System bus broadcast *

*)

Keyboard control (SimpleBox, ParameterBox, PotentiometerBox) is disabled,
parameterisation is still possible.

**) If the communication during keyboard control is interrupted (time out 0.5 sec), the

FI will disable without an error message.

NOTE:

For details of the optional bus systems, please refer to the relevant supplementary bus manuals
(BU02x0).

-

www.nord.com

As an alternative to setting the parameter, System Bus can also be selected with DIP switch 3.

P510

... [-01]

... [-02]

Setpoint source

S

0 ... 4

{ [-01] = 0 }

{ [-02] = 0 }

Selection of the setpoint source to be parameterised.

… [-01] = Main setpoint source

… [-02] = Subsidiary setpoint source

Selection of the interface via which the FI receives the setpoint.

0 = Auto: The setpoint source is automatically derived

from the setting in the parameter P509 >Control
word source<.

1 = Control terminals, digital and analog inputs

control the frequency, including fixed frequencies

2 = USS

3 = System bus

4 = System bus broadcast

P513

Telegram time-out

S

-0.1 / 0.0 /
0.1 ... 100.0 sec

{ 0.0 }

Monitoring function of the active bus interface. Following receipt of a valid telegram, the next
one must arrive within the set period. Otherwise the FI reports an error and switches off with the
error message E010 >Bus Time Out<.

0.0 = Off: Monitoring is switched off.

-0.1 = no error: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Box removed, etc.), the FI will continue to operate unchanged.

Note:

In BUS mode (e.g.: PROFIBUS DP), monitoring is controlled via parameter (P120). Settings in
parameter (P513) therefore have no effect.

Exception: Setting {-0,1}