NORD Drivesystems BU0220 User Manual

Page 25

Advertising
background image

2 Assembly and installation

BU 0220 GB-0912

Subject to technical amendments

25

Control connection details

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

1

24V

2

24V supply

(Module, field and system
bus level)

24VDC ±20%

≈ 90 mA
reverse polarity protected


Max. permissible current
load: 500mA

Connection of the sensor supply
voltage

via DC/DC converter to Terminal
11.

-

Potential isolation

3

PB B

(incoming)

4

(outgoing)

PBR B
Bus + (red lead)

RxD/TxD-N

RS485 transfer

The use of twisted, shielded two-
conductor cable / Type A Profibus
cable is highly recommended

-

5

PB A

(incoming)

6

(outgoing)

PBR A
Bus - (green lead)

RxD/TxD-P

-

7

0V-B

8

Data ground bus

Reference potential for
internal Profibus voltage
supply

-

9

RTS

Ready to send

-

10

5V B

5V bus supply
voltage

Internal Profibus voltage
supply

Note: Must not be used externally!

-

Potential isolation

11

24V

12

13

24V supply

(Module, field and system
bus level)

As for terminal 1

However, max.
permissible current load:
3A

Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 to DIN4)

-

15

0V

17

18

GND
Reference potential
for digital signals

-

14

Sys +

System bus

data cable +

System bus
interface

-

16

Sys -

System bus

data cable -

-

19

DIN1

Digital input 1

(I/O Profibus DIN1)

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF
Scan rate 1 ms

Inputs as per EN 61131-2
Type 1

Each digital input has a reaction
time of 1ms.

P174

20

DIN3

Digital input 3

(I/O Profibus DIN3)

P174

Advertising