7 PROFIBUS DP data transfer

BU 0220 GB-0912

Subject to technical amendments

61

7.2.1.1 Control word (STW)

The control word (STW) is the first word transferred to the frequency inverter in the process data section in an
order telegram. For example, a control word "Ready for switch-on" corresponds to 047E

(hex)

. The FI is

ultimately enabled with 047F

(hex)

.

PZD1

PZD2

PZD3

PZD4

STW

SW1

SW2/3

SW2/3

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Meaning of the individual bits:

Bit

Value

Meaning

Remarks

0

0

OFF 1

Reverse with the brake ramp, with disconnection from supply at f=0Hz

1

ON

Ready for operation

1

0

OFF 2

Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is disabled.

1

Operating condition

OFF 2 is cancelled

2

0

OFF 3

Quick stop with programmed quick stop time; with disconnection from supply at
f=0Hz; the FI switches to starting disabled condition.

1

Operating condition

OFF 3 is cancelled

3

0

Disable operation

Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is enabled.

1

Enable operation

The output voltage is enabled; ramp to the existing setpoint

4

0

Lock ramp generator

Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI remains
in the operation enabled state.

1

Operating condition

Enable ramp generator

5

0

Stop ramp generator

The setpoint currently provided by the ramp generator is "frozen" (frequency is
maintained).

1

Enable ramp generator Enable setpoint on ramp generator

6

0

Disable setpoint

Selected setpoint value is set to zero on the ramp generator.

1

Enable setpoint

Selected ramp generator setpoint is activated.

7

0

No acknowledgement

With the switch from 0 to 1, errors which are no longer active are acknowledged.

1

Acknowledge

Note: When a digital input has been programmed for the "ack.fault" function, this
bit must not permanently be set to 1 via the bus (otherwise, edge evaluation
would be prevented).

8

0

1

Bit 8 active

Bus bit 8 from the control word is set. (only for SK 200E and SK 500E)
For further details of function, please refer to parameter (P480) and Section 7.2.1.7.

9

0

1

Bit 9 active

Bus bit 9 from the control word is set. (only for SK 200E and SK 500E)
For further details of function, please refer to parameter (P480) and Section 7.2.1.7.

10

0

PZD invalid

The transmitted process data is invalid.

1

PZD valid

Valid process data is transferred from the master.
Note: If only setpoints are transferred via the bus, this bit must be set so that the
transferred setpoint is valid.

11

0

1

Rotational direction:
right

Rotational direction right (priority) ON*

12

0

1

Rotational direction:
left

Rotational direction left ON*

13

0/1

Reserved

14

0/1

Bit 0 to switch
parameter set

00 = Parameter set 1
01 = Parameter set 2

10 = Parameter set 3
11 = Parameter set 4

15

0/1

Bit 1 to switch
parameter set

* If Bit 12=0, then "Direction of rotation right ON" applies