6.2.2

Table of possible error messages in the bus module

The following error messages concern bus-related messages, which are indicated on the PROFIBUS DP
module (SK CU4-PBR or SK TU4-PBR(-

…)).

Display

in the SimpleBox

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P170

E1000

1000

EEPROM error

Module faulty

1010

System bus 24V missing

Check connections and supply cables

Ensure 24V voltage supply

1020

System bus timeout

Check physical bus connections

FI has been switched off

1030

System bus OFF

Check physical bus connections

5000

PROFIBUS ASIC error

Profibus system error (ASIC cannot be accessed)

5010

PROFIBUS address incorrect Comply with address range 3 ... 125

5020

PROFIBUS timeout

Telegram transfer is faulty.