2 enable with 50% setpoint – NORD Drivesystems BU0220 User Manual

Page 74

Advertising
background image

PROFIBUS DP

– Supplementary manualfor NORD Frequency Inverter SK 2xxE

74

Subject to technical amendments

BU 0220 GB-0912

7.3.2

Enable with 50% setpoint

A frequency inverter in the "Standby" status must be enabled for clockwise rotation with 50% setpoint. The
PPO type 1 (Section 7.2) is used, however only the PZD channel is considered.

Procedure:

1) Check last status word (e.g. ZSW 0B 31)

2) Generate control word (STW 04 7F) and specify setpoint (SW1 20 00 (=50%))

3) Check response telegram (ZSW 0B 37, IW1 20 00)

Procedure - Details

1) Check last status word (e.g. ZSW 0B 31)

word

5

6

Byte

8

9

10

11

Designation

ZSW

IW1

Value

0B

31

00

00

2) Generate control word (STW 04 7F) and specify setpoint (SW1 20 00 (=50%))

word

5

6

Byte

8

9

10

11

Designation

STW

SW1

Value

04

7F

20

00

The frequency inverter accelerates the motor in the ramp. When the inverter reaches 50% setpoint, it
responds with the following telegram.

3) Check response telegram (ZSW 0B 37, IW1 20 00)

word

5

6

Byte

8

9

10

11

Designation

ZSW

IW1

Value

0B

37

20

00