7 PROFIBUS DP data transfer

BU 0220 GB-0912

Subject to technical amendments

63

7.2.1.3 Setpoint 1 (SW1)

The function of the first setpoint is set in the parameter "Function bus setpoint 1" (SK 200E: (P546[01]) or
SK 500E: (P546)) (see relevant frequency inverter manual).

In the order telegram, setpoint 1 follows immediately after the control word. Setpoint 1 is pre-set to the transfer
of a setpoint frequency (16 bit value).

PZD1

PZD2

PZD3

PZD4

STW

SW1

SW2

SW3

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

The setpoint is transferred as an integer in the range -32768 to 32767 (8000 hex to 7FFF hex), whereby 16384
(4000 hex) is exactly 100% and -16383 (C000 hex) corresponds to -100%. Due to this resolution, setpoints
(depending on function) of up to ± 200% can be transferred.

A setpoint of 100% corresponds to the respective nominal value:

Setting

100% is equal to

Off

Setpoint frequency, actual frequency PID, actual
frequency PID limited, actual frequency PID monitored,
frequency addition, frequency subtraction, maximum
frequency

Maximum frequency

Torque current limit

Torque current limit (P112)

Current limit

Inverter rated current

Servo mode torque

Rated torque

Torque precontrol

Torque precontrol (P214)

7.2.1.4 Setpoints 2 and 3 (SW2/3)

If the PPO type 2 or 4 is used, in addition to setpoint 1, a second setpoint can be transferred in word PZD3 and
a third setpoint in PZD4.

PZD1

PZD2

PZD3

PZD4

STW

SW1

SW2

SW3

The definition of these two setpoints corresponds to that of setpoint 1.

However, the transfer of a third (maximum 16 Bit) setpoint is only possible if the other two setpoints are also 16
Bit values.

If the transfer of a 32 bit setpoint is necessary (Example: setpoint position), this must be divided into two 16 bit
values, i.e. into two PZDs (position High and Low word). It does not matter in which of the three process
data words (PZD2 and above) the two position words are transferred.

The definition in the frequency inverter can then, for example, be made via the parameters:

PZD3:

Bus function - setpoint 2" (SK 200E / SK 54xE: (P546[-02]) or SK 500E (P547)) and

PZD4:

Bus function - setpoint 3" (SK 200E / SK 54xE: (P546[-03]) or SK 500E (P548))