PROFIBUS DP

– Supplementary manualfor NORD Frequency Inverter SK 2xxE

52

Subject to technical amendments

BU 0220 GB-0912

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P173

Module status

0 ... FFFF (hex)

Possible values:

Bit 0 = Bus status

“PREOPERATIONAL” (PROFIBUS DP initialisation active)

Bit 1 = Bus status

“OPERATIONAL” (Data exchange active)

Bit 2 = Node-guarding timeout (PROFIBUS DP master watchdog)
Bit 3 = Timeout (time in P151)
Bit 4 = Module system error
Bit 5 = Reserved
Bit 6 = System

bus “BUS WARNING”

Bit 7 = System

bus “BUS OFF”

Bit 8 = Status FI 1
Bit 9 = Status FI 1
Bit 10= Status FI 2
Bit 11= Status FI 2
Bit 12= Status FI 3
Bit 13= Status FI 3
Bit 14= Status FI 4
Bit 15= Status FI 4

Status for FI x:
Bit High

Bit Low Status

0

0

FI is offline

0

1

unknown FI

1

0

FI is online

1

1

FI missing or switched off

P174

Digital inputs

0 ... 15

Instantaneous view of input level logic.

Possible values:

Bit 0= Input 1 (DIN1 of the bus module)
Bit 1= Input 2 (DIN2 of the bus module)
Bit 2= Input 3 (DIN3 of the bus module)
Bit 3= Input 4 (DIN4 of the bus module)

P175

Digital outputs

0 ... 3

Instantaneous view of output level logic.

Possible values:

Bit 1= Output 1 (DO1 of the bus module)
Bit 2= Output 2 (DO2 of the bus module)