NORD Drivesystems BU0220 User Manual

Page 35

Advertising
background image

3 Displays and diagnosis

BU 0220 GB-0912

Subject to technical amendments

35

Underside of SK 200E

8x DIP switches

Alternatively, diagnosis can be performed via a Windows PC with the aid of NORD CON software (available free of
charge from

www.nord.com

). The necessary connection cable (RJ12 - SUB D9) is available from Getriebebau

Nord GmbH as part number 278910240. If necessary, an interface converter from SUB D9 to USB2.0 is
commercially available.

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

Accessory cable (optional) for PC connection

Adapter cable
RJ12 to SUB-D9

... for direct
connection to a PC
with NORD CON
software

Length 3m

Assignment RS 232
(RxD, TxD, GND)

Part. No. 278910240

TxD

RxT

GND

+24V

n.c.
n.c.

Assignment of SUBD9 connector:

Pin2: RS232_TxD

Pin3: RS232_RxD

Pin5: GND

RxD

GND

TxD

6

1

5

9

No special settings are required to set up communication with the individual diagnostic tools.

The allocation of addresses is defined via the system bus addressing. The display of the diagnostic tool is
according to the following table, whereby the frequency inverter which is directly connected to the diagnostic
tool is automatically assigned the address

“0”.

Device

External

technology unit

Frequency inverter

with address 32

(system bus)

Frequency inverter

with address 34

(system bus)

Frequency inverter

with address 36

(system bus)

Frequency inverter

with address 38

(system bus)

USS

address

30

1

2

3

4

Note
Setting of the system bus address is carried out via two DIP
switches (DIP 1 and 2) on the underside of the SK 200E-
frequency inverter. For further details, please refer to the frequency
inverter manual (BU 0220). The address of the BUS module is
defined as “30”.