6 electrical installation, Electrical installation, Safety engineering – Lenze 8400 motec Manual User Manual

Page 108

Advertising
background image

Safety engineering

Electrical installation

8

l

108

EDS84DG752 EN 4.0

8.6

Electrical installation

X61 − connection of safety system "Safety Option 10"

Pin

Connection

Description

DO

SIB GI

SIA

X61

24O

DC 24 V

(+19.2 … +28.8 V)

+

-

"

Terminal strip, 5−pole

E84DG027

SIA

Safe input, channel A

SIB

Safe input, channel B

GI

GND potential for SIA/SIB
GND potential for the unsafe signalling output

24O

24 V voltage supply for the unsafe signalling output

DO

Unsafe signalling output: "SafeTorqueOff" with a 2−channel
request by SIA andSIB

X61

E84DG025

X61

a

[mm]

[mm

2

]

[AWG]

Safety

55

0.5 ... 1.5

20 ... 16

0.5 ... 1.0

20 ... 18

0.5

20

)

Note!

The wiring connected for test purposes to the connections of the safety system
must be removed (e.g. bridges SIA/SIB at 24O).