Commissioning

Quick commissioning
General configuration settings

6

l

82

EDS84DG752 EN 4.0

Preconditions for initial switch−on

ƒ

The wiring unit is mounted and wired according to the instructions,

– directly on a motor clamping flange or

– with the wall adapter on a suitable surface near the motor.

ƒ

Connections with the mains, motor, holding brakes, etc. have been established.

ƒ

The communication unit has been mounted and wired according to the scheduled
application.

– Input and output signals

– Safe input

– Fieldbus

(depending on the version, only available optionally)

ƒ

If required, the basic settings for "local mode" have been carried out.

– DIP switches

– Potentiometer

ƒ

The drive unit has been mounted and screwed together.

ƒ

Use available control functions reasonably, e.g.

– Inhibit controller enable

– Set speed adjustment to the minimum setting

– Activate safety system

ƒ

The use of a brake resistor has been checked.

– In the case of dynamic loads or difficult control conditions, the use of the internal

brake resistor E84DZEW47R0 is always recommended for the devices
E84DGDVB4024 ... 7524 (4 ... 7.5 kW).

}

Danger!

High hazard potential during commissioning
Incorrect settings may cause unexpected and dangerous motor and system
movements.
Possible consequences:

ƒ

Damage to material assets

ƒ

Injury to persons

Protective measures:

ƒ

Clear hazardous area

ƒ

Observe safety instructions and safety clearances