4 operation with rated mains voltage 480 v, Operation with rated mains voltage 480 v, Technical data – Lenze 8400 motec Manual User Manual

Page 37

Advertising
background image

Technical data

Rated data

Operation with rated mains voltage 480 V

4

l

37

EDS84DG752 EN 4.0

4.2.4

Operation with rated mains voltage 480 V

Basis of the data

Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

3/PE AC

480

432 − 0 % ... 528 + 0 %

45 − 0 % ... 65 + 0 %

Mains current

Output power

Motor power

at I

arated

U, V, W

4 pol. ASM

Type

I

Lrated

[A]

S

arated

[kVA]

P

arated

[kW]

E84DGDVB3714

1.1

0.8

0.37

E84DGDVB5514

1.5

1.1

0.55

E84DGDVB7514

2.0

1.5

0.75

E84DGDVB1124

2.7

2.1

1.1

E84DGDVB1524

3.1

2.4

1.5

E84DGDVB2224

4.6

3.5

2.2

E84DGDVB3024

5.9

4.5

3.0

E84DGDVB4024

7.7

5.7

4.0

E84DGDVB5524

10.6

7.9

5.5

E84DGDVB7524

13.5

10.0

7.5

Output currents [A] at switching frequency

2 kHz

4 kHz

8 kHz

16 kHz

Type

I

arated2

I

aM2

I

arated4

I

aM4

I

arated8

I

aM8

I

arated16

I

aM16

E84DGDVB3714

1.1

2.2

1.1

2.2

0.7

1.3

E84DGDVB5514

1.5

3.0

1.5

3.0

1.0

1.8

E84DGDVB7514

2.0

4.0

2.0

4.0

1.3

2.4

E84DGDVB1124

2.7

5.4

2.7

5.4

1.8

3.2

E84DGDVB1524

3.2

6.4

3.2

6.4

2.1

3.8

E84DGDVB2224

4.7

9.4

4.7

9.4

3.1

5.6

E84DGDVB3024

6.0

12.0

6.0

12.0

4.0

7.2

E84DGDVB4024

7.9

15.8

7.9

15.8

5.3

9.5

E84DGDVB5524

10.8

21.6

10.8

21.6

7.2

13.0

E84DGDVB7524

13.7

27.4

13.7

27.4

9.1

16.4

I

aNx

Rated value of continuous output current

I

aMx

Maximum output current (overload current)

l

Periodic load change of 3 s with I

aMx

and recovery time of 12 s according to

the tables under chapter

^ 4.4

l

Can be obtained in the setting "x kHz fixed/..." in C00018

Switching
frequency

If the maximum heatsink temperature is reached, the switching frequency is
reduced to 4 kHz.
In the setting "x kHz var./..." in C00018 the switching frequency is reduced
depending on the output current.
Depending on the switching frequency and e.g. the ambient temperature, it
may be required to reduce the output current (chapter 4.1, operating
conditions).

Advertising