Technical data, General data and operating conditions – Lenze 8400 motec Manual User Manual

Page 27

Advertising
background image

Technical data

General data and operating conditions

4

l

27

EDS84DG752 EN 4.0

Protection of persons and equipment

Enclosure

EN 60529

IP65
optional: IP66

in ready−for−use state:

l

Close unused bores for cable
glands with blanking plugs!

l

Close unused connectors with
protection covers or blanking
plugs!

NEMA 250

Protection according to

l

Type 4

(Earth) leakage current

EN 61800−5−1

> 3.5 mA AC, > 10 mA DC

Observe the regulations and
safety instructions!

Total fault current

In TN systems the following earth−leakage circuit breakers
can be used:

Motor mounting

E84DGDVB3714

...

E84DGDVB1524

30 mA, type B

E84DGDVB2224

...

E84DGDVB7524

300 mA, type B

Wall mounting

E84DGDVB3714

...

E84DGDVB7524

300 mA, type B

Additional equipotential
bonding

M5 thread with terminal in the WU for connection of a
16mm

@ PE cable

Protective insulation of
control circuits

EN 61800−5−1

Safe isolation from mains by double (reinforced) insulation

Insulation resistance

EN 61800−5−1

Site altitude

0 ... 2000 m Overvoltage category III

2000 ... 4000 m Overvoltage category II

Short−circuit strength

EN 61800−5−1

Connection:

Motor

To a limited extent, the
controller is inhibited, error
acknowledgement required

Motor holding brake, brake
resistor

No

PTC, control terminals

Full

Earth−fault strength

EN 61800−5−1

Connection:

Motor (at controller
enable)

To a limited extent, the
controller is inhibited, error
acknowledgement required

Motor (during operation)

No

Brake resistor, PTC

No

Protective measures
against

l

Short circuit on the motor side at switch−on and during
operation

l

Motor stalling

l

Motor overtemperature
– Input for PTC or thermal contact
– I

2

t monitoring

Cyclic mains switching

l

Switchings/minute

3

l

Switchings/hour

Max. 20

l

Switching pause

After switching the mains 3
times in one minute, there must
be a switching pause of
9 minutes.

Starting current

£ 2 x I