Installation

Mechanical installation

5

l

60

EDS84DG752 EN 4.0

5.3

Mechanical installation

ƒ

If the cooling air is polluted (fluff, (conductive) dust, soot, aggressive gases), take
adequate countermeasures, as e.g.:

– Regular cleaning of the cooling ribs at the controller

– Separate air guide

ƒ

Possible mounting position:

– Observe information on mounting conditions in the chapter "Technical data".

ƒ

Maintain the specified free spaces above and below the controller to other
installations!

ƒ

Ensure untroubled cooling and exhaust air flow.

– Arrangement of several devices only to the sides

For mounting, use the screws of the motor terminal box. The installation material must
ensure a durable mechanical connection.

If screws must be replaced, we recommend the following, depending on the motor frame
size:

ƒ

M4/M5/M6 cheese head screw, hexagon socket, according to DIN 912/ISO 4762

ƒ

M4/M5/M6 cheese head screw, torx, according to ISO 14579