Commissioning, Quick commissioning general configuration settings, Possible settings with dip1 – Lenze 8400 motec Manual User Manual

Page 79: Possible settings with dip2

Advertising
background image

Commissioning

Quick commissioning

General configuration settings

6

l

79

EDS84DG752 EN 4.0

Possible settings with DIP1

(Lenze setting bold)

DIP1

Switch

Description

1

2

3

4

5

6

7

8

Settings after DIP1, DIP2, P1, P2, and
P3 active

on ( I )

ON

off ( 0 )

OFF

Direction of rotation

left

ON

right

OFF

Control

quadratic

ON

linear

OFF

Flying restart circuit

on ( I )

ON

off ( 0 )

OFF

Reserved

OFF

OFF

OFF

Message type −> on
(only optional with Communication
Unit "+ Safety")

fail −> DO
ready −> NO (relay)

ON

ready −> DO
fail −> NO (relay)

OFF

Possible settings with DIP2

DIP2

Switch

Description

1

2

3

4

5

6

7

8

Rated motor frequency

50 Hz

OFF

OFF

60 Hz

ON

OFF

87 Hz

OFF

ON

120 Hz

ON

ON

Mode of the analog input
(only optional with Communication
Unit "+ Safety")

0 ... 10 V

OFF

OFF

0 ... 20 mA

ON

OFF

4 ... 20 mA

OFF

ON

not permissible

ON

ON

Control mode of technology
application
(cf. selection C00007)

9 (local mode)

OFF

OFF

OFF

10 (terminals 0)

ON

OFF

OFF

12 (terminals 2)

OFF

ON

OFF

14 (terminals 11)

ON

ON

OFF

16 (terminals 16)

OFF

OFF

ON

Reserved

ON

OFF

ON

Reserved

OFF

ON

ON

40 (MCI)

ON

ON

ON

Reserved

OFF