Technical data, Overcurrent operation – Lenze 8400 motec Manual User Manual
Page 41
Advertising
![background image](/manuals/565652/41/background.png)
Technical data
Overcurrent operation
l
41
EDS84DG752 EN 4.0
Type
I
amax
/I
aN8
[%]
in
15−s cycle
f = 2 kHz
f = 4 kHz
f = 8 kHz
f = 16 kHz
0
1
0
1
0
1
0
1
E84DGDVB3714
−
−
200
75
200
75
120
50
E84DGDVB5514
E84DGDVB7514
E84DGDVB1124
E84DGDVB1524
E84DGDVB2224
E84DGDVB3024
E84DGDVB4024
E84DGDVB5524
E84DGDVB7524
Type
I
amax
/I
aN8
[%]
in
180−s cycle
f = 2 kHz
f = 4 kHz
f = 8 kHz
f = 16 kHz
2
3
2
3
2
3
2
3
E84DGDVB3714
−
−
150
75
150
75
100
50
E84DGDVB5514
E84DGDVB7514
E84DGDVB1124
E84DGDVB1524
E84DGDVB2224
E84DGDVB3024
E84DGDVB4024
E84DGDVB5524
E84DGDVB7524
I
Tip!
For calculations of application−specific cycles please contact your Lenze contact
person.
Advertising