Commissioning

Quick commissioning

6

l

76

EDS84DG752 EN 4.0

6.2

Quick commissioning

(

Stop!

Automatic motor start
In "Local mode" The auto−start option "Inhibit at power−on" is not set. When
the mains is connected, the motor starts if the controller enable RFR is bridged
or set.
("Local mode" => DIP1/1 = ON and DIP2/5−7 = OFF)
Possible consequences:

ƒ

Danger or damages through unexpected motor start.

Protective measures:

ƒ

Decouple the motor from the drive train during commissioning phase.

ƒ

Replace the factory−set bridge at RFR by an NO contact.

ƒ

Do not set controller enable.