Commissioning
Quick commissioning
l
76
EDS84DG752 EN 4.0
6.2
Quick commissioning
(
Stop!
Automatic motor start
In "Local mode" The auto−start option "Inhibit at power−on" is not set. When
the mains is connected, the motor starts if the controller enable RFR is bridged
or set.
("Local mode" => DIP1/1 = ON and DIP2/5−7 = OFF)
Possible consequences:
ƒ
Danger or damages through unexpected motor start.
Protective measures:
ƒ
Decouple the motor from the drive train during commissioning phase.
ƒ
Replace the factory−set bridge at RFR by an NO contact.
ƒ
Do not set controller enable.