2 wiring of brake resistor, Wiring of brake resistor, Braking operation – Lenze 8400 motec Manual User Manual

Page 96

Advertising
background image

Braking operation

Braking operation with brake resistor
Wiring of brake resistor

7

l

96

EDS84DG752 EN 4.0

7.2.2

Wiring of brake resistor

{

Danger!

Hazardous electrical voltage
During operation of the standard device and up to 3 minutes after power−off
hazardous electrical voltages may occur at the terminals of the brake resistor.
Possible consequences:

ƒ

Death or severe injuries when touching the terminals.

Protective measures:

ƒ

Disconnect the standard device from the mains before working on the brake
resistor.

ƒ

Check all power terminals for isolation from supply.

ƒ

Select the mounting location so that the operating conditions mentioned in
the mounting instructions for the brake resistor are permanently
guaranteed.

}

Danger!

Hot surface
The brake resistor may get very hot. (For temperatures see the mounting
instructions for the brake resistor.)
Possible consequences:

ƒ

Severe burns when touching the brake resistor.

ƒ

Fire or smouldering fire if flammable material is placed near the brake
resistor or may get to it.

Protective measures:

ƒ

Before working on the brake resistor, check its surface temperature.

ƒ

Select the mounting location so that the operating conditions mentioned in
the mounting instructions for the brake resistor are permanently
guaranteed.

ƒ

Protect the mounting location through fire prevention.

Protect the brake resistor and controller against destruction caused by overload:

ƒ

Establish a safety shutdown using the thermostat of the brake resistor to disconnect
the controller from the mains.

Connecting cable version

ƒ

up to 0.5 m: twisted and unshielded

ƒ

from 0.5 to 5 m: shielded

– Use shielded cables to meet the EMC requirements.

Advertising