2 digital output, 3 analog input, 4 connection of relay output – Lenze 8400 motec Manual User Manual
Page 50: Digital output, Analog input, Connection of relay output, Technical data
Technical data
Control terminals
Digital output
l
50
EDS84DG752 EN 4.0
4.7.2
Digital output
X4
Pin / name
Features
Rated value
DO1
Digital output
24 V DC
50 mA
4.7.3
Analog input
The analog input is only available with the modules
ƒ
Communication in the "Advanced" version or
ƒ
Standard I/O.
X4
Pin / Name
Feature
Rated value
AU
GND
Voltage input
0 ... 10 V
Input resistance
> 80 k
W
Sampling frequency
80 Hz (12 ms)
Accuracy
± 0.1 V
Electric strength of external voltage
−7 ... +30 V
A/D converter
10 bit resolution
AI
GND
Current input, parameterisable
0.6 ... +20 mA (I < 0.6mA
¢
"0")
4 ... +20 mA, fail−safe
Input resistance
250
W
Input current in case of open circuit
Display "0" (I < 0.6 mA)
Sampling frequency
80 Hz (12 ms)
Accuracy
± 0.2 mA
Electric strength of external voltage
−7 ... +7 V
A/D converter
10 bit resolution
4.7.4
Connection of relay output
X4
Pin / name
Features
Rated value
COM
NO
Switching contact, NO contact,
potential−free
24 V DC, 2 A
not inductive
250 V AC, 2 A