Commissioning

Diagnostics

Drive diagnostics via the integrated display

6

l

93

EDS84DG752 EN 4.0

6.6

Diagnostics

6.6.1

Drive diagnostics via the integrated display

On the top side of the Drive Unit, a green/red LED display indicates the respective
operating status of the controller. The LED shines brightly through the transparent cap.

LED status display

Description

green

red

Mains off

off

off

Switch−on phase (initialisation)

(shining yellow)

on

on

Operation or motor data identification

on

off

Controller inhibited (RFR)

blinking

Safety function active (Safe torque off)

flashing

Controller is ready (initialisation completed)

flashing twice

Operation with warning active

on

blinking

flashing twice

flashes every 3 s

Quick switch−off active

on

flashing

System error

off

on

Error

blinking

Message is active

flashing

LED flashes once approx. every 3 seconds (slow flash)

LED flashes once approx. every 1.25 seconds (flash)

LED flashes twice approx. every 1.25 seconds (double flash)

LED blinks every second

LED is permanently on

6.6.2

Diagnostic codes

Important codes for diagnostics

In addition to the keypad, also use the LEDs on the front of the controller for drive
diagnostics:

ƒ

Two LEDs indicate the device status (DRIVE READY and DRIVE ERROR)

ƒ

Two LEDs indicate the bus status (CAN−RUN and CAN−ERROR)

The LEDs for the bus status are less important during quick commissioning.

I

Tip!

The handling of the keypad X401 or the diagnosis terminal X401 is described
in the operating instructions. The instructions are supplied with the keypad
and are also included in electronic form on the product CD "L−force Inverter
Drives 8400".