4 technical data, 1 general data and operating conditions, Technical data – Lenze E84AYCIB User Manual

Page 17: General data and operating conditions, E84aycib communication manual (interbus), 4technical data

Advertising
background image

EDS84AYCIB EN 4.0 - 11/2010

L

17

E84AYCIB communication manual (INTERBUS)

Technical data

General data and operating conditions

4

Technical data

4.1

General data and operating conditions

"Inverter Drives 8400" hardware manual
This manual contains data on the ambient conditions and the electromagnetic

compatibility (EMC) that also apply to the communication module.

Field

Values

Order designation

• E84AYCIBV (coated version)

• E84AYCIBS: (standard version)

Communication profile

INTERBUS

Interfaces

• Input (IN): 9-pole Sub-D plug

• Output (OUT): 9-pole Sub-D socket

Communication medium

RS485

Network topology

Ring

Type of node

INTERBUS slave

Number of nodes

• 1 master

• 512 slaves

Baud rate

500 kbps or 2 Mbps

(can be set via DIP switch or code)

Max. cable length

• 400 m at 500 kbps

• 150 m at 2 Mbps

(between the individual INTERBUS nodes)

Process data words (PD) to be used

0 ... 10: 16 bits/word

(can be set via DIP switch or code)

Parameter data words (PCP)

0, 1, 2, 4: 16 bits/word

(can be set via DIP switch or code)

Max. number of data words

10 (PD + PCP): 16 bits/word

Max. PDU length

64 bytes

INTERBUS identification (module ID) • 3 = 0x3 (PCP 0 words)

• 227 = 0xE3 (PCP 1 word)

• 224 = 0xE0 (PCP 2 words)

• 225 = 0xE1 (PCP 4 words)

Voltage supply

External supply via the 2-pole plug connector

• "+": U = 24 V DC (21.6 V - 0 % … 26.4 V + 0 %), I

max

= 180 mA

• "-": Reference potential for external voltage supply

Conformities, approvals

CE

Advertising