C13892 | pcp - length, C13893 | process data length, C13892 – Lenze E84AYCIB User Manual

Page 67: C13893, For t, E84aycib communication manual (interbus)

Advertising
background image

EDS84AYCIB EN 4.0 - 11/2010

L

67

E84AYCIB communication manual (INTERBUS)

Parameter reference

Parameters of the communication module

C13892

C13893

Parameter | Name:

C13892 | PCP - length

Data type: UNSIGNED_8

Index: 10683

d

= 29BB

h

Setting of the number of the parameter data words to be used (PCP)

The setting is activated ...

• if all DIP switches (S205) are in the "OFF" position;

• after executing the "11: Save start parameters" device command via standard device code C00002 and

performing another mains switching of the communication module/drive afterwards.



Setting the number of parameter data words (PCP) ( 36)

Selection list

(Lenze setting printed in bold)

0 No PCB data
1 1 word
2 2 words
4 4 words

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13893 | Process data length

Data type: UNSIGNED_8

Index: 10682

d

= 29BA

h

Setting of the number of the process data words to be used (PD)

The setting is activated ...

• if all DIP switches (S205) are in the "OFF" position;

• after executing the "11: Save start parameters" device command via standard device code C00002 and

performing another mains switching of the communication module/drive afterwards.



Setting the number of process data words (PD) ( 35)

Selection list

(Lenze setting printed in bold)

0 No process data
1 1 word
2 2 words
3 3 words
4 4 words
5 5 words
6 6 words
7 7 words
8 8 words
9 9 words

10 10 words

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT