Commissioning

Possible settings through DIP switch

6.2.1

Setting the number of process data words (PD)

 The number of process data words (PD) can be set via switches 1 ... 4 or code

C13893

(for this, see

Settings in the »Engineer«

( 38)

).

 0 ... 10 process data words can be used.
 The current setting is displayed in

C13860/2

.

Note!

The data word sum (PD + PCP) must amount to 1 ... 10 words. Impermissible

settings are reported by the LED "BE" (red blinking).



LED status displays

( 54)

The communication module then continues to operate internally with the

following values:
• PD = 2 (words)
• PCP = 1 (word)

DIP switch

Number of

PD

Switch

Max. number

of PCP

1

2

3

4

0

OFF

OFF

OFF

OFF

4

1

OFF

OFF

OFF

ON

2

OFF

OFF

ON

OFF

3

OFF

OFF

ON

ON

4

OFF

ON

OFF

OFF

5

OFF

ON

OFF

ON

6

OFF

ON

ON

OFF

7

OFF

ON

ON

ON

2

8

ON

OFF

OFF

OFF

9

ON

OFF

OFF

ON

1

10

ON

OFF

ON

OFF

0

12345678

ON

OFF