1 setting the number of process data words (pd), Setting the number of process data words (pd), E84aycib communication manual (interbus) – Lenze E84AYCIB User Manual
Page 35

EDS84AYCIB EN 4.0 - 11/2010
L
35
E84AYCIB communication manual (INTERBUS)
Commissioning
Possible settings through DIP switch
6.2.1
Setting the number of process data words (PD)
The number of process data words (PD) can be set via switches 1 ... 4 or code
).
0 ... 10 process data words can be used.
The current setting is displayed in
.
Note!
The data word sum (PD + PCP) must amount to 1 ... 10 words. Impermissible
settings are reported by the LED "BE" (red blinking).
The communication module then continues to operate internally with the
following values:
• PD = 2 (words)
• PCP = 1 (word)
DIP switch
Number of
PD
Switch
Max. number
of PCP
1
2
3
4
0
OFF
OFF
OFF
OFF
4
1
OFF
OFF
OFF
ON
2
OFF
OFF
ON
OFF
3
OFF
OFF
ON
ON
4
OFF
ON
OFF
OFF
5
OFF
ON
OFF
ON
6
OFF
ON
ON
OFF
7
OFF
ON
ON
ON
2
8
ON
OFF
OFF
OFF
9
ON
OFF
OFF
ON
1
10
ON
OFF
ON
OFF
0
12345678
ON
OFF