4 specification of the bus cable, 5 bus cable length, Specification of the bus cable – Lenze E84AYCIB User Manual

Page 30: Bus cable length, E84aycib communication manual (interbus)

Advertising
background image

E84AYCIB communication manual (INTERBUS)

Installation

Electrical installation

30

L

EDS84AYCIB EN 4.0 - 11/2010

5.2.4

Specification of the bus cable

5.2.5

Bus cable length

Adapt the baud rate according to the bus cable length:

Note!

Only use cables that meet the listed specifications.

Specification of the INTERBUS cable
Cable type

Sold by the meter

(e.g. PHOENIX CONTACT: IBS RBC meter-T, order no. 28 06 28 6)

No. of conductors

3 x 2, twisted in pairs, with joint shielding

Conductor cross-section

> 0.2 mm

2

DC-cable resistance

< 96 Ω/km

Impedance (characteristic)

• 120 Ω ± 20 % (f = 64 kHz)

• 100 Ω ± 15 Ω (f > 1 MHz)

Capacitance per unit length

< 60 nF/km (f = 800 Hz)

Baud rate

Cable length between the individual INTERBUS nodes

500 kbps

Max. 400 m

2 Mbps

Max. 150 m

Note!

Select the baud rate which depends on the data volume, cycle time, and number

of nodes only as high as required for the application.

Advertising