4 specification of the bus cable, 5 bus cable length, Specification of the bus cable – Lenze E84AYCIB User Manual
Page 30: Bus cable length, E84aycib communication manual (interbus)

E84AYCIB communication manual (INTERBUS)
Installation
Electrical installation
30
L
EDS84AYCIB EN 4.0 - 11/2010
5.2.4
Specification of the bus cable
5.2.5
Bus cable length
Adapt the baud rate according to the bus cable length:
Note!
Only use cables that meet the listed specifications.
Specification of the INTERBUS cable
Cable type
Sold by the meter
(e.g. PHOENIX CONTACT: IBS RBC meter-T, order no. 28 06 28 6)
No. of conductors
3 x 2, twisted in pairs, with joint shielding
Conductor cross-section
> 0.2 mm
2
DC-cable resistance
< 96 Ω/km
Impedance (characteristic)
• 120 Ω ± 20 % (f = 64 kHz)
• 100 Ω ± 15 Ω (f > 1 MHz)
Capacitance per unit length
< 60 nF/km (f = 800 Hz)
Baud rate
Cable length between the individual INTERBUS nodes
500 kbps
Max. 400 m
2 Mbps
Max. 150 m
Note!
Select the baud rate which depends on the data volume, cycle time, and number
of nodes only as high as required for the application.