E84aycib communication manual (interbus) – Lenze E84AYCIB User Manual

Page 29

Advertising
background image

EDS84AYCIB EN 4.0 - 11/2010

L

29

E84AYCIB communication manual (INTERBUS)

Installation

Electrical installation

Assignment of the 9-pole Sub-D plug X206 (IN)

Assignment of the 9-pole Sub-D socket X207 (OUT)

Pin

Designation

Input/output

Description

1

DO1

Input

RS485: DO1 not inverted

2

DI1

Output

RS485: DI1 not inverted

3

GND

Reference potential

4

Free

Not assigned

5

Vcc5

Output

5 V DC

6

/DO1

Input

RS485: DO1 inverted

7

/DI1

Output

RS485: DI1 inverted

8

Vcc5

Output

5 V DC

9

Free

Not assigned

Pin

Designation

Input/output

Description

1

DO2

Output

RS485: DO2 not inverted

2

DI2

Input

RS485: DI2 not inverted

3

GND

Reference potential

4

GND

5

Vcc5

Output

5 V DC

6

/DO2

Output

RS485: DO2 inverted

7

/DI2

Input

RS485: DI2 inverted

8

Vcc5

Output

5 V DC

9

RBST

Signalling input

Connection to the outgoing INTERBUS is plugged.