Monitoring

10

Monitoring

Communication fault

 If INTERBUS communication is interrupted, e.g. due to cable break or INTERBUS master

failure, no process data are transmitted to the slave in the

"

IBS-ACTIVE

"

( 57)

status.

 After the time to be parameterised by the user in

C13881

has elapsed, the response

parameterised in

C13880/1

is executed in the controller.

Settings in the »Engineer«

Under the Settings tab in the »Engineer« you can set the following parameters:

Reaction on interrupted INTERBUS communication (

C13880/1

)

Delete process data (

C13885

)

– Setting of the process data which the controller is to process further for maintaining

internal communication when the INTERBUS has failed.

Monitoring time for INTERBUS communication failure (