E84AYCIB communication manual (INTERBUS)

Commissioning

Possible settings through DIP switch

36

L

EDS84AYCIB EN 4.0 - 11/2010

6.2.2

Setting the number of parameter data words (PCP)

 The number of parameter data words (PCP) can be set via switches 5 and 6 or code

C13892

(for this, see

Settings in the »Engineer«

( 38)

).

 0, 1, 2 or 4 parameter data words can be used.
 The current setting is displayed in

C13860/1

.

Note!

The data word sum (PD + PCP) must amount to 1 ... 10 words. Impermissible

settings are reported by the LED "BE" (red blinking).



LED status displays

( 54)

The communication module then continues to operate internally with the

following values:
• PD = 2 (words)
• PCP = 1 (word)

DIP switch

Number of PCP

Switch

Max. number of

PD

ID code

[hex]

5

6

0

OFF

OFF

10

0x03

1

OFF

ON

9

0xE3

2

ON

OFF

8

0xE0

4

ON

ON

6

0xE1

12345678

ON

OFF