Commissioning
Possible settings through DIP switch
36
L
EDS84AYCIB EN 4.0 - 11/2010
6.2.2
Setting the number of parameter data words (PCP)
The number of parameter data words (PCP) can be set via switches 5 and 6 or code
0, 1, 2 or 4 parameter data words can be used.
The current setting is displayed in
.
Note!
The data word sum (PD + PCP) must amount to 1 ... 10 words. Impermissible
settings are reported by the LED "BE" (red blinking).
The communication module then continues to operate internally with the
following values:
• PD = 2 (words)
• PCP = 1 (word)
DIP switch
Number of PCP
Switch
Max. number of
PD
ID code
[hex]
5
6
0
OFF
OFF
10
0x03
1
OFF
ON
9
0xE3
2
ON
OFF
8
0xE0
4
ON
ON
6
0xE1
12345678
ON
OFF