E84aycib communication manual (interbus) – Lenze E84AYCIB User Manual

Page 32

Advertising
background image

E84AYCIB communication manual (INTERBUS)

Installation

Electrical installation

32

L

EDS84AYCIB EN 4.0 - 11/2010

Assignment of the X205 plug connector

Terminal data

Designation

Explanation

+

U = 24 V DC (21.6 V - 0 % … 26.4 V + 0 %)

I = 180 mA

-

Reference potential for external voltage supply

Field

Values

Electrical connection

2-pole plug connector with spring connection

Possible connections

Rigid:

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

Flexible:

Without wire end ferrule

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

With wire end ferrule, without plastic sleeve

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

With wire end ferrule, with plastic sleeve

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

Stripping length

10 mm