2 possible settings through dip switch, Possible settings through dip switch, Possible settings through dip switch ( 34) – Lenze E84AYCIB User Manual

Page 34: E84aycib communication manual (interbus)

Advertising
background image

E84AYCIB communication manual (INTERBUS)

Commissioning

Possible settings through DIP switch

34

L

EDS84AYCIB EN 4.0 - 11/2010

6.2

Possible settings through DIP switch

[6-1]

DIP switch

E84YCIB001D

The following can be set through the DIP switch

(S205):

 Number of process data words (PD)

Switches: 1 ... 4

( 35)

 Number of parameter data words (PCP)

Switches: 5 and 6

( 36)

 Baud rate

Switch: 8

( 37)

Lenze setting: All switches "OFF"
Switch 7 has no function.

Note!

To make any modified settings take effect, switch the voltage supply of the

communication module off and then on again.



Initial switch-on

( 39)

The settings can also be made via codes:
• All DIP switches = "OFF" (Lenze setting):

At switch-on, the configuration from codes

C13892

,

C13893

, and

C13894

becomes active.

• At least one DIP switch = "ON":

At switch-on, the values are accepted from the switch positions.

The data word sum (PD + PCP) may maximally amount to 10 words.