Wiring the device modules – Lenze E94ASHExxxx User Manual

Page 106

Advertising
background image

Wiring the device modules

Communication modules

6

106

EDK94SH366 DE/EN/FR/ES/IT 3.1

DIP switch

Pos.

Description

A

Addressing of the station

For addressing purposes, every station must be given an unambiguous address.
Valid address range: 1 126
The address can be set freely via the front-panel switch.

Note!

ƒ

For S1 - S7 = OFF (Lenze setting):
When switching on the module, the configuration set under code C00899

becomes active.

ƒ

For one of the switches S1 - S7 = ON:
When switching on the module, the address resulting from the switch

setting becomes active.

Switch off the voltage supply of the communication module and then on again

in order to activate changed settings.

Address settings through the DIP switch (device front)
The sum of the values (identical with package labelling) results in the station address to be

set:
Example:

Switch

S7

S6

S5

S4

S3

S2

S1

Package labelling

«64»

«32»

«16»

«8»

«4»

«2»

«1»

Switch state

0

0

1

0

1

1

1

Address (= 23)

0

0

16

0

4

2

1

Displays

Pos.

Colour

Condition

Description

MS

Green

Blinking

Communication module is supplied with voltage, but has no

connection to the standard device (standard device is switched off,

initialising or does not exist).

On

Communication module is supplied with voltage and has

established a connection to the standard device.

ME

Red

On

An error occurred concerning the communication module.

BS

Green

Blinking

Communication via the communication module is established. The

PROFIBUS is active.

BE

Red

On

Bus monitoring has responded.

DE

Red

On

The communication module is not accepted by the standard device

(see notes given in the documentation for the standard device)