Wiring the device modules
Communication modules
6
106
EDK94SH366 DE/EN/FR/ES/IT 3.1
DIP switch
Pos.
Description
A
Addressing of the station
For addressing purposes, every station must be given an unambiguous address.
Valid address range: 1 … 126
The address can be set freely via the front-panel switch.
Note!
ƒ
For S1 - S7 = OFF (Lenze setting):
When switching on the module, the configuration set under code C00899
becomes active.
ƒ
For one of the switches S1 - S7 = ON:
When switching on the module, the address resulting from the switch
setting becomes active.
Switch off the voltage supply of the communication module and then on again
in order to activate changed settings.
Address settings through the DIP switch (device front)
The sum of the values (identical with package labelling) results in the station address to be
set:
Example:
Switch
S7
S6
S5
S4
S3
S2
S1
Package labelling
«64»
«32»
«16»
«8»
«4»
«2»
«1»
Switch state
0
0
1
0
1
1
1
Address (= 23)
0
0
16
0
4
2
1
Displays
Pos.
Colour
Condition
Description
MS
Green
Blinking
Communication module is supplied with voltage, but has no
connection to the standard device (standard device is switched off,
initialising or does not exist).
On
Communication module is supplied with voltage and has
established a connection to the standard device.
ME
Red
On
An error occurred concerning the communication module.
BS
Green
Blinking
Communication via the communication module is established. The
PROFIBUS is active.
BE
Red
On
Bus monitoring has responded.
DE
Red
On
The communication module is not accepted by the standard device
(see notes given in the documentation for the standard device)