Wiring the device modules – Lenze E94ASHExxxx User Manual

Page 119

Advertising
background image

Wiring the device modules

Safety modules

6

119

EDK94SH366 DE/EN/FR/ES/IT 3.1

Connections

Pos.

Description

Safety address switch (in the left part of the housing)

S82

Module switch for parameter set adoption from the memory module

X82.1

Plug-in terminal strips for input and output signals

X82.2
X82.3
X82.4

Addressing
The safety address serves to the clear assignment of the safety modules of the SM301 type

in systems with several drives. The address ”0” is not permissible.

Address switch
The safety address can be set in the left part of the housing by means of the DIP switch .

For setting the switch, use an appropriately small tool, e. g. a probe. The switch can only be

set if the module is not connected to a basic device. Via the switch, addresses in the range

of 0 ... 1023 can be set. Alterations by the switch with regard to the address only are

activated when the 24-V supply is switched on. The address setting ”0” requires the setting

by the address code.

DIP switch

Labelling

1

2

3

4

5

6

7

8

9

0

Value of the address bit

1

2

4

8

16

32

64

128

256

512

Note!

In the SM301 safety module as of version VA 1.xx, the address 0 is replaced as

follows:

ƒ

With the address saved in the safety module in the parameter

”Safety address” (C15111).

ƒ

If the address 0 canot be replaced, the module reports an error.