Wiring the device, Power terminals, Mains – Lenze E94ASHExxxx User Manual

Page 93: Motor temperature monitoring, Motor brake control (optional)

Advertising
background image

Wiring the device

Power terminals

5

93

EDK94SH366 DE/EN/FR/ES/IT 3.1

Mains

Terminal X100

Marking

Description

Connection with ring

cable lug for M10

L1

L2

L3

Connection of the mains phases

SSP94KL801

Connection for the PE conductor on the supply side

Terminal data

Max. conductor cross-section

Tightening torque

Screw drive

[mm

2

]

[AWG]

[Nm]

[lb-in]

Device size 8:

E94ASxE1724

E94ASxE2024

2 x 240

2 x 500 mcm

19

168

WAF 16

Device size 9:

E94ASxE2454

E94ASxE2924

E94ASxE3664

Motor temperature monitoring

Terminal X106

Labelling

Description

T1

T2

Motor temperature monitoring with PTC element (type-A sensor,

switching performance according to EN 60947-8 for type-A tripping

units) or thermostat (NC contact).

SSP94X6106

Terminal data

Max. conductor cross-section

Tightening torque

Screw drive

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

2.5

12

0.5 ... 0.6

4.5 ... 6.2

Slot

0.6 x 3.5

With wire end

ferrule

Motor brake control (optional)

Terminal X107

Labelling

Description
Connection of the motor holding brake

BD1

BD2

+ (Lenze: WH)

- (Lenze: BN)

E94AZHY0101: 24 V DC, max. 5.0 A

Observe correct polarity!

+ / -

Supply voltage for the motor holding brake (18 ... 30 V DC)

Observe correct polarity!

SSP94X6107

Terminal data

Max. conductor cross-section

Tightening torque

Screw drive

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

2.5

12

0.5 ... 0.6

4.5 ... 6.2

Slot

0.6 x 3.5

With wire end

ferrule

Advertising