Wiring the device, Power terminals, Mains – Lenze E94ASHExxxx User Manual
Page 93: Motor temperature monitoring, Motor brake control (optional)
Wiring the device
Power terminals
5
93
EDK94SH366 DE/EN/FR/ES/IT 3.1
Mains
Terminal X100
Marking
Description
Connection with ring
cable lug for M10
L1
L2
L3
Connection of the mains phases
SSP94KL801
Connection for the PE conductor on the supply side
Terminal data
Max. conductor cross-section
Tightening torque
Screw drive
[mm
2
]
[AWG]
[Nm]
[lb-in]
Device size 8:
E94ASxE1724
E94ASxE2024
2 x 240
2 x 500 mcm
19
168
WAF 16
Device size 9:
E94ASxE2454
E94ASxE2924
E94ASxE3664
Motor temperature monitoring
Terminal X106
Labelling
Description
T1
T2
Motor temperature monitoring with PTC element (type-A sensor,
switching performance according to EN 60947-8 for type-A tripping
units) or thermostat (NC contact).
SSP94X6106
Terminal data
Max. conductor cross-section
Tightening torque
Screw drive
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
2.5
12
0.5 ... 0.6
4.5 ... 6.2
Slot
0.6 x 3.5
With wire end
ferrule
Motor brake control (optional)
Terminal X107
Labelling
Description
Connection of the motor holding brake
BD1
BD2
+ (Lenze: WH)
- (Lenze: BN)
E94AZHY0101: 24 V DC, max. 5.0 A
Observe correct polarity!
+ / -
Supply voltage for the motor holding brake (18 ... 30 V DC)
Observe correct polarity!
SSP94X6107
Terminal data
Max. conductor cross-section
Tightening torque
Screw drive
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
2.5
12
0.5 ... 0.6
4.5 ... 6.2
Slot
0.6 x 3.5
With wire end
ferrule