IT system

Stop!

Overvoltage on components:
In case of an earth fault in IT systems, incompatible overvoltages may occur in

the plant.
Possible consequences:
Destruction of the device.
Protective measures:
When using the devices in IT systems, separate the internal connection of

filters to the protective earth. For this purpose carry out the device-specific

measure as described.

How to separate the internal connection of filters to the protective earth:
1. Remove the upper housing cover.
2. The S300 switch can be found on the Interface card. The Interface card is located in

the top of the device.
– ON position: Standard operation at earthed-neutral systems (Lenze).
– OFF position: Operation at IT systems.

3. Push the S300 switch into the OFF position.

94ITSW8001

ON - Standard

OFF - IT

IF-Card-SW

IF-Card-SW