Wiring the device – Lenze E94ASHExxxx User Manual

Page 92

Advertising
background image

Wiring the device

Power terminals

5

92

EDK94SH366 DE/EN/FR/ES/IT 3.1

External brake resistor

Terminal X105

Marking

Description

Connection with ring

cable lug for M8

Rb1

Rb2

Connection of external brake resistor

SSP94KL801

Terminal data

Max. conductor cross-section

Tightening torque

Screw drive

[mm

2

]

[AWG]

[Nm]

[lb-in]

Device size 8:

E94ASxE1724

E94ASxE2024

2 x 240

2 x 500 mcm

9.5

84

WAF 13

Device size 9:

E94ASxE2454

E94ASxE2924

E94ASxE3664

DC bus

Terminal X100

Marking

Description

Connection with ring

cable lug for M8

+UG

-UG

Alternative option for DC-bus voltage connection (compatible to

9300 series).

SSP94KL801

Terminal data

Max. conductor cross-section

Tightening torque

Screw drive

[mm

2

]

[AWG]

[Nm]

[lb-in]

Device size 8:

E94ASxE1724

E94ASxE2024

2 x 240

2 x 500 mcm

9.5

84

WAF 13

Device size 9:

E94ASxE2454

E94ASxE2924

E94ASxE3664

Tip!

Now mount the barrier between mains input and power terminals, if had been

removed to have more free space for wiring.