Wiring the device modules

Safety modules

6

113

EDK94SH366 DE/EN/FR/ES/IT 3.1

SM100
Function

ƒ

Safe torque off
(previously: safe standstill, protection against unexpected start-up)

SSP94SM112

Fig.6-9

E94AYAB safety module

Connections

Pos.

Labelling

Description

X80

SI1

Input first shutdown path

GI

GND potential for SI1/SI2

SI2

Input second shutdown path

GO

GND potential feedback

24O

24 V voltage supply feedback

DO1

Non-safe signalling output “Safe pulse inhibit”

Terminal data

Conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Rigid

0.14 ... 1.5

26 ... 16

Spring terminal

With wire end

ferrule

0.25 ... 0.5

24 ... 20

Displays

Pos.

Colour

Condition

Description

EN

Yellow

On

Controller enabled

Off

Non-safe display ”Safe pulse inhibit”

DE

Red

On

The module is not accepted by the standard device (see notes

given in the documentation for the standard device).