Wiring the device modules – Lenze E94ASHExxxx User Manual

Page 114

Advertising
background image

Wiring the device modules

Safety modules

6

114

EDK94SH366 DE/EN/FR/ES/IT 3.1

SM300
Functions

ƒ

Safe torque off (STO)
(previously: safe standstill, protection against unexpected start-up)

ƒ

Safe stop 1 (SS1)

ƒ

Connection of safety sensors

ƒ

PROFIsafe safety bus connection

SSP94SM317

Fig.6-10

E94AYAD safety module

Please observe the following safety instructions and application notes to preserve the

certified safety engineering features and to ensure trouble-free and safe operation.

Danger!

Danger to life through improper installation
Improper installation of the safety engineering systems can cause an

uncontrolled restart of the drives.
Possible consequences:

ƒ

Death or severe injuries

Protective measures:
Total cable length between X82 and the connected components (e.g. sensors,

devices, etc.) > 3 m:

ƒ

It is essential to shield the cable installed between X82 and the connected

components:

– Connect the shield at least to the shield support of the installation

backplane.

– If possible, connect the shield to the connected component as well.

Total cable length between X82 and the connected components (e.g. sensors,

devices, etc.) < 3 m:

ƒ

Unshielded wiring is permitted.