Wiring the device modules

Safety modules

6

116

EDK94SH366 DE/EN/FR/ES/IT 3.1

X82.3

Labelling

Description

GCL

GND clock output

GI2

GND IN I2A/I2B

I2B

Sensor input 2, channel B (only for passive sensors)

I2A

Sensor input 2, channel A (only for passive sensors)

GCL

GND clock output

GI1

GND I1A/I1B

I1B

Sensor input 1, channel B (only for passive sensors)

I1A

Sensor input 1, channel A (only for passive sensors)

n. c.

This terminal is not assigned.

X82.4

Labelling

Description

GCL

GND clock output

GI4

GND I4A/I4B

I4B

Sensor input 4, channel B (only for active sensors)

I4A

Sensor input 4, channel A (only for active sensors)

n. c.

This part of the terminal strip is not assigned.

Sensor input 3 is not available.

n. c.
n. c.
n. c.
n. c.

Cable cross-sections and tightening torques
Type

[mm

2

]

[Nm]

AWG

[lb-in]

Wire end ferrule,

insulated

0.25 ... 0.5

Spring terminal

24 ... 20

Spring terminal

Rigid

0.14 ... 1.5

26 ... 16

Stripping length or contact length: 9 mm