Wiring the device

Important notes

5

83

EDK94SH366 DE/EN/FR/ES/IT 3.1

5

Wiring the device

5.1

Important notes

Danger!

All power terminals carry hazardous voltages up to 20 minutes after mains

disconnection.

Danger!

Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800-5-1. Especially:

– Fixed installation

– PE connection must conform to standards (PE conductor diameter

≥ 10 mm

2

or PE conductor must be connected twice)

Stop!

The device contains components that can be destroyed by electrostatic

discharge!
Before working on the device, personnel must ensure that they are free of

electrostatic charge by using appropriate measures.

Stop!

No device protection in the event of too high mains voltages
The mains input is not fused internally.
Possible consequences:

ƒ

Destruction of the device if the mains voltage is too high.

Protective measures:

ƒ

Observe the max. permissible mains voltage.

ƒ

Fuse the device correctly on the supply side against mains fluctuations and

voltage peaks.