2 segment cable length, Segment cable length, Control technology | canopen communication manual – Lenze CANopen control technology User Manual

Page 23

Advertising
background image

DMS 4.2 EN 07/2011 TD17

L

23

Control technology | CANopen communication manual

Technical data

Bus cable length

5.4.2

Segment cable length

The segment cable length is determined by the used cable cross-section and the number of

nodes. Repeaters divide the total cable length into segments. Without a repeater, the

segment cable length corresponds to the total cable length.

Example: Selection help

Max. number of

nodes per segment

Cable cross-section (interpolation is permissible)

0.25 mm

2

(AWG 24)

0.50 mm

2

(AWG 21)

0.75 mm

2

(AWG 19)

1.00 mm

2

(AWG 18)

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

100

150 m

270 m

410 m

600 m

Given:
Total cable length to be

implemented

200 m

Number of nodes

63

Results
Max. possible baud rate

250 kbps

(derived from table

Total cable length ( 22)

)

Required cable cross-section

(interpolated)

0.30 mm

2

(AWG23)

(derived from table

Segment cable length ( 23)

)

Cable cross-section - standard CAN

cable

0.34 mm

2

(AWG22)



Bus cable specification ( 21)