Planning the CANopen network

Device specifications of the field devices

36

L

DMS 4.2 EN 07/2011 TD17

Basic identifier - ECS servo system
The default setting of the basic identifier is as follows:

1) When the boot-up identifier is set manually, observe the use of heartbeat because of the same COB-ID.

Devices with two active parameter data channels (SDO) respond with a fieldbus scan in the

address range 1 ... 127 with two node addresses each (with offset 64).

Object

Direction

Basic identifier

from the drive

to the drive

dec

hex

NMT

0

0

Sync

128

80

PDO1

(process data channel 1)

TPDO1

z

384

180

RPDO1

z

512

200

PDO2

(process data channel 2)

TPDO2

z

640

280

RPDO2

z

641

281

PDO3

(process data channel 3)

TPDO3

z

768

300

RPDO3

z

769

301

SDO1

(parameter data channel 1)

TSDO1

z

1408

580

RSDO1

z

1536

600

SDO2

(parameter data channel 2)

TSDO2

z

1472

5C0

RSDO2

z

1600

640

Heartbeat

z

1792

700

Boot-up 1)

z

1792

700